A permanent magnet holds the plunger after the pulse ends, so the 12 V rail supplies the move — not the hold.
In a battery-powered lock, a meter or a remote valve, the expensive part of the energy budget is not the actuation, it is the holding. A spring-return solenoid has to stay energised for as long as the mechanism must remain open; a latching solenoid does not. A permanent magnet retains the plunger at the end of the stroke, and the coil draws current only during the pulse that moves it.
That shifts the design problem to the drive. A bi-stable part needs the current direction reversed between set and reset; a single-direction part relies on a mechanical bias for the return. The pulse is short — typically 20 ms to 120 ms — and the capacitor that supplies it is often more important than the battery behind it.
A bi-stable latching solenoid needs the current direction to change between set and reset. An H-bridge or a two-relay circuit does that; a single low-side MOSFET does not. Decide the drive before the part, not after.
A 12 V, 5.76 W coil at 25 % ED draws about 0.5 A. Over 100 ms that is 50 mC, easily supplied by a 1000 µF capacitor — which lets a small battery deliver a large pulse without a deep voltage sag.
The 40 N figure of the X40180 is what the magnet retains with the coil off. The force available to move the bolt during the pulse depends on the air gap and is lower. Size the mechanism on the pull force and the shock resistance on the holding force.
Locks for lockers, cabinets and access control normally need a mechanical release for power failure or service. Plan the lever or cam into the housing, not onto the solenoid.
| Model | Construction | Stroke | Force | Voltage |
|---|---|---|---|---|
| X40180 | Square Latching Solenoid | 4 mm | up to 40 N | 6 / 12 V DC |
| KS1139L/S | Bi-Directional Latching Solenoid | 5 mm curve range | 0.5 kgf | to order |
| KS1225L/S | Bi-stable latching KS1225L/S | — | 200 gf | to order |
| X1010L | Cabinet Lock Solenoid, 5 V | 3 mm | up to 10 N | 5 V DC |
Values are catalogue figures at the stated duty cycle. The force that matters is the force at your working gap — request the curve for the model you shortlist.
Yes, that is the point of the type. A permanent magnet retains the plunger, so the holding current is zero and the battery only supplies the pulse.
Only if the part is a single-direction latching type with a mechanical return. Bi-stable parts need the polarity reversed between the two positions.
Stay within the rated maximum ON time, typically 0.1 s to 0.3 s on these frames. A longer pulse heats the coil without adding force, and on a small frame it can demagnetise the latch over time.
That depends on the holding force against the worst-case shock load. For vehicle or locker doors, specify a holding force two to three times the calculated shock load rather than the static load.